MIPP-NOTE-HARD-22
Peter Barnes, LLNL
Version 0.3
March 28, 2005

E907 TPC

Power-On / Power-Off Procedures
Emergency Procedures
Expert Contact Information

Abstract

This note explains

How to Turn On/Turn Off:

How to Ramp Up/Down:

How to Check the Gas System for normal operation.

In Case of Emergency:

How to Contact the Experts.


TPC Water

The TPC Water system skid is 10 m upstream of the TPC on the west side, next to the BCKOV2 head. The picture below identifies the main controls and gauges.

Turning ON the TPC Water

To turn ON the TPC Water:

  1. Turn ON the chiller.
    The switch is on the front panel; toggle it up to START, then release it to ON.
    • The numeric display shows the current water temperature.
    • The chiller setpoint temperature is 20°.
    • To check the setpoint hold down the SETPOINT button, which displays the setpoint on the numeric display.
    • To adjust the setpoint, hold down the SETPOINT button while adjusting the knob. Set it to 20°.
  2. Turn ON the circulation pump.
    The switch is the red one on the green motor speed control box near the floor. Toggle it up to START, then release it to ON.
    • The numeric display shows the current pump speed.
    • The pump speed setpoint is nominally 36, but should be adjusted to achieve the proper flow rate in step 3, below.
    • To adjust the speed turn the SPEED knob.
  3. Check the flow rate.
    The flow meter above the pump should read 15 gpm.
    • If it does not, adjust the pump speed as in step 2, above.
  4. Check for leaks.
    Take a quick look for leaks:
    • In the hose connections at the back of the water skid.
    • In the hose connections at the front of the TPC for the main supply/return and the cross-over manifolds.
    • Under the TPC.
    If leaks are found, turn off the water system.
[Image: Photo of Chiller Sled with controls labeled.]

Turning OFF the TPC Water

In the case of

  1. turn off the water system,
  2. CALL an EXPERT.

To turn OFF the TPC Water:

  1. Turn OFF the circulation pump.
  2. Turn OFF the chiller.

Contents


TPC Low Voltage Power Supplies

The TPC Low Voltage power supplies are just upstream of JGG in RR07-RR08 on the east side and RR09-RR10 on the west side. The pictures below identify the switches in RR07-RR08.

Turning ON the TPC Low Voltage Power Supplies

To turn ON the TPC Low Voltage supplies:

  1. Turn ON the Chiller and Pump.
  2. Turn ON the AC POWER MASTER SWITCH.
    The switch is on the 2U panel near the top of RR07.
  3. Reset the CLK and WATER interlocks.
    Initially the CLK and WATER lamps will be lit on the LOW VOLTAGE P.S. MASTER INTERLOCK. To reset these interlocks, press the RESET button below each lamp.
  4. Reset the interlock chain for each rack.
    At each rack (RR07-RR10), press any RESET button on any EOS TPC POWER SUPPLY. You may have to hold the RESET button for a second to get all the supplies in the rack to latch, or you may need to try a short press. ;)
  5. Verify that all enabled supplies are on.
    The A, B, C, D, trouble lamps on the LOW VOLTAGE P.S. MASTER INTERLOCK are illuminated when an enabled power supply channel is off. When all enabled channels are latched on, the lamps goes off.

[Image: Photo of RR07-RR08 with controls labeled.]
[Image: Photo of RR07-RR08 with controls labeled.]

Turning OFF the TPC Low Voltage Power Supplies

In the case of

  1. Turn OFF the TPC Low Voltage Power Supplies.
  2. For any water leak at the TPC turn OFF the Water system.
  3. CALL an EXPERT.

To turn OFF the TPC Low Voltage power supplies:

  1. Turn off all EOS TPC POWER SUPPLIES.
    Press the P.S. SHUTDOWN button on the LOW VOLTAGE P.S. MASTER INTERLOCK.
  2. Turn off the AC POWER MASTER SWITCH.

Contents


VME Crates

The VME Crates are located in RR04-RR05 upstream of the JGG on the east side. The picture below identifies the switches in RR04-RR05.

Turning ON the VME Crates

To turn ON the VME Crates:

  1. Turn ON each crate using the black switch at the bottom of the front panel.
    If the crate does not turn on, check the position of the red switch on the back, which must also be on.

[Image: Photo of VME Crates with switches labeled.]

Turning OFF the VME Crates

In the case of

  1. Turn OFF the VME Crates,
  2. CALL an EXPERT.

To turn OFF the VME Crates:

  1. Turn off each crate using the black switch at the bottom of the front panel.

Contents


Cathode High Voltage Supply

The Cathode High Voltage Supply is located in RR04 upstream of the JGG on the east side. The supply is near the bottom of the rack. The picture below identifies the controls on the front panel.

Turning ON the Cathode High Voltage Supply

To turn ON the Cathode High Voltage Supply:

  1. Turn ON the Cathode High Voltage Supply using the black power switch on the left side of the chassis.
  2. Enable the high voltage output, using the red switch on the right side of the chassis.

[Image: Photo of Cathode High Voltage Supply.]

Ramping the Cathode Voltage

To ramp the Cathode voltage manually:

  1. Turn ON the Cathode supply.
  2. Set the current limit to 0.12 mA.
    To set the current limit
    1. Press the LIMIT button.
    2. Press the CURRENT button.
    3. Set 0.12 mA on the display using the knob.
    4. Press the ENTER button.
  3. To ramp the voltage in steps:
    1. Press the SET button.
    2. Press the VOLTS button.
    3. Set the desired voltage on the display using the knob.
    4. Press the ENTER button.

    Suggested voltage steps and nominal current for a dry chamber with nitrogen gas:

    Voltage
    (V)
    Current
    (mA)
    100 0.0013
    1000 0.0085
    3000 0.0245
    5000 0.0408
    7000 0.0568
    8000 0.0647
    9000 0.0927
    9500 0.0767
    10,000 0.0805

    After each step, wait for the current to settle to within 0.0002 of the expected value before proceeding to the next step. (The field cage resistor ladder is 124 MΩ, which sets the current at each voltage.)

    If the supply trips (because of the current limit), it sets the output to 0 V. You can "catch" it before it gets all the way down by quickly noting the approximate voltage and entering a new set voltage that is nearby. For example, if you note the voltage is 3567 V and dropping, set the voltage to anything in the approximate range 3000-4000 V and you should be able to clear the trip and keep the cathode from ramping completely down. Then restart the step ramp at the next step voltage.

  4. To ramp the voltage continuously:
    1. Press the ADJUST button.
    2. Press the VOLTS button.
    3. Control the voltage directly using the knob.
      CAUTION: The knob is rate sensitive. Small twitches can cause VERY large changes in the setting, causing the current limit to trip.
      ". . . the [cathode] need[s] love and a steady hand . . ."
    4. When you reach the desired voltage, press the ENTER button.

To ramp the Cathode voltage automatically:

  1. If not already running (it should be!) start TPC_Cathode_control on e907hv.

    The control program runs only on e907hv.fnal.gov. To run the program, you have to be the daq user, and in the right area:

    1. $ su daq
    2. e907hv{daq}:~> cd ~/hv_control/
    3. e907hv{daq}:~> TPC_Cathode_control

  2. Set the voltage and current limits.

    There is no read back of the limits. The program displays the last value set by this invocation. The only reliable way to ensure that the limits have not been set incorrectly (e.g., by another instance of the program) is to set them explicitly.

    1. Type L, then enter 10100 when prompted for the new voltage limit.
    2. Type U, then enter 100 when prompted for the new current limit.

  3. Set the voltage to an initial value, by typing V, then entering 50 when prompted for the voltage.
  4. If the high voltage output is not already ON, type O (letter 'O') and confirm.
  5. Ramp the voltage by typing P, then enter the desired voltage. Normal cathode voltage is 10000 (10 kV).

Turning OFF the Cathode Voltage

In the case of

  1. Turn OFF the Cathode HV supply,
  2. CALL an EXPERT.

To turn OFF the Cathode HV supply:

  1. Turn off the high voltage output, using the red switch on the right side of the chassis.
    If sparking persists turn off the Anode supply.
  2. Monitor the cathode voltage.
  3. When the cathode voltage is <50 V turn off the supply using the black switch on the left side of the chassis.

Contents


Anode High Voltage Supply

The Anode high voltage supply is the LeCroy 1440 HV chassis at the bottom of RR05, upstream of the JGG on the east side. The picture below identifies the switches on the front panel.

Turning ON the Anode High Voltage Supply

To turn ON the Anode HV supply:

CAUTION: This supply is used by the T0 counters, the BCKOV counters, the TPC, the CKOV, and the TOF. Be careful only to modify settings for the intended detector.
  1. Turn ON the AC POWER switch, the large white one at the bottom of the chassis.
  2. Press the HV ENABLE button, at the center of the right-hand large module. This should illuminate the READY lamp.

[Image: Photo of LeCroy 1440 High Voltage supply.]

Ramping the Anode Voltage

Note:

  1. If already running (it should be!) stop hv_monitor on e907hv.

    The control and monitoring programs run only on e907hv.fnal.gov. They don't share the serial interface nicely, so you have to stop the monitor program (with a ^C) before starting the control program. To run the program, you have to be the daq user, and in the right area:

    1. $ su daq
    2. e907hv{daq}:~> cd ~/hv_control/
    3. e907hv{daq}:~> hv_control

  2. Log in as the TPC Detector (3). Ask a local expert for the password.
  3. If the mainframe is OFF, turn it on by typing O.
    CAUTION: This will apply voltage to all the other detectors sharing this mainframe. Check with experts and/or the weekly coordinator to be sure you should be doing this!.
  4. Load and program the TPC parameters:
    1. Type L to load the parameter file. Enter tpc-param.hv as the parameter file.
    2. Type P to program the mainframe with the new parameters.
  5. Check that the anodes have no shorts:
    1. Ramp each card to 20 volts by typing ^R.
      The TPC (usually) uses cards 12 and 13. When prompted, enter the card number, then the voltage (20).
    2. When the ramp is complete, display the card by typing C. Verify that each channel has a read back current less than 5 counts. It make take ~10  for the read back to settle down, especially if the TPC has been open to air. Refresh the card display by typing R.
  6. Load the standard voltage file by typing L. tpc.hv should be a symbolic link to the current settings. Ask an expert for help in deciding if this file is correct.
  7. Ramp the TPC by typing ^R.
  8. After the ramp is complete, verify that each channel has come up to the set voltage, and that all currents are less than 10 counts.
  9. Restart the monitoring program, hv_monitor.

Resetting Tripped Anodes

  1. Check that the beam rate is reasonable. T01 should be < 50K per spill. If the rate is to high, ask MCR to reduce it.
  2. Stop the hv_monitor program and go to the hv_control program.
  3. Type T to invoke the "Reset TPC" function.
  4. You will be prompted for the new voltage for each tripped channel, and shown the previous setting. The normal voltage for most channels is 1250 V.
    1. If a channel trips more than twice in two hours, reduce the setting by 50 V.
    2. Otherwise, enter the previous setting.
  5. Log in CRL which channels tripped, what voltag they were at, and what voltage they were reset to.

Turning OFF the Anode High Voltage Supply

In the case of

  1. Turn OFF the Anode supply,
  2. CALL an EXPERT.

To turn OFF the Anode supply:

  1. Press the HV ENABLE button to extinguish the READY lamp.
  2. Turn OFF the AC POWER switch.

Contents


TPC Gas System

The TPC gas rack is located upstream of the JGG on the west side, near to RR09. The picture below identifies the relevant gauges.

Normally the gas system should only be operated by an expert. Shifters should check the gas system regularly.

To CHECK the Gas system under normal flow conditions:

  1. Verify that the raw supply pressure on PI-01 is in the 3-7 psi range.
  2. Verify that the regulated pressure on PI-03 is in the 1.8-2.2 psi range.
  3. Verify that the TPC inlet pressure on PI-02 is in the 0.45-0.5 inches of water range.
    If this pressure is > 1 inch of water then
    turn off the Gas system.
  4. Verify that the TPC outlet pressure on PI-04 is in the 0-0.2 inches of water range.
    If this pressure is > 1 inch of water then turn off the Gas system.
  5. Verify that the rotameter ball on FI-01 is in the 100-120 mm range.
  6. Verify that the MAIN BUBBLER, B1 is actively bubbling.

In case

  1. CALL an EXPERT.

[Image: Photo of TPC Gas Rack with valves and gauges labeled.]

Turning OFF the Gas System

In the case of

  1. Turn OFF the Gas system,
  2. CALL an EXPERT.

To turn OFF the Gas system:

  1. Close the P10 supply valve, MV-03, by turning the short (arrow) side of the handle to the OFF label.
  2. CALL an EXPERT.

Contents


Expert Contact Information

Expert email Phone
Preferred Backup 1 Backup 2
Peter Barnes pdbarnes@llnl.gov 925-422-3384 (W) 510-610-0366 (C) 510-526-0365 (H)
Mike Heffner mheffner@llnl.gov 925-422-6762 (W) 925-961-0657 (H)  
         
Phone locations: (W) work, (C) cell, (H) home.

PDB, 3/28/04 Valid XHTML 1.0!